Both switch a circuit off so it can be worked on safely. The difference is what else they do.
A fused isolator (switch fuse) switches the circuit off and protects the cable after it with a fuse. A non-fused isolator only switches off, so the circuit must already be protected upstream. Use fused for a new supply off the meter tails, non-fused for local isolation.
- A fused isolator, usually called a switch fuse, isolates the circuit and has a fuse inside that protects the cable after it against overcurrent.
- A non-fused isolator, sometimes called a switch disconnector, only isolates. It gives no protection, so the circuit has to be protected somewhere else.
Pick the wrong one and you either pay for protection you don't need, or leave a cable unprotected.
When to use a fused isolator
Use a switch fuse when the cable leaving it needs protecting and nothing upstream is doing that job at the right rating.
The classic example is at the meter. You need a second supply off the meter tails for a garage, an outbuilding, an EV charger or a solar install. The tails are protected by the supplier's main fuse, but that might be 80A or 100A, far too big for a smaller sub-main cable. A switch fuse with a suitably rated fuse gives you a lockable off switch and protects the new cable.
The Wylex DSF60M is a typical one: a double pole switch rated 100A, with a 60A cartridge fuse fitted, in a lockable metal enclosure. It also comes with an 80A fuse (DSF80M) or a 100A fuse (DSF100M).
When to use a non-fused isolator
Use a plain isolator when the circuit is already protected upstream, by an MCB or RCBO in the consumer unit, and you just need a safe local point to switch it off.
Common examples:
- Ahead of a consumer unit or EV charger. The Wylex REC2S is a 100A double pole isolator in a small enclosure, lockable off.
- Outdoor kit like heat pumps and air con units. A rotary isolator next to the unit lets an engineer lock it off while they work. The Gewiss rotary isolators come in 16A to 63A, 4 pole.
- Extractor fans. A fan with a timer has a permanent live and a switched live, so it needs a triple pole isolator that breaks both lives and the neutral. The Hager WMPS3PI and Click CMA020 are 10A fan isolators, commonly fitted outside the bathroom.
Wylex DSF60MSwitch fuse, 60A fuse fittedSee live stock →
Wylex REC2S100A double pole isolatorSee live stock →
Gewiss GW70436P32A 4 pole rotary isolatorSee live stock →
Hager WMPS3PI10A triple pole fan isolatorSee live stock →
Side by side
| Fused (switch fuse) | Non-fused (isolator) | |
|---|---|---|
| Switches the circuit off | Yes | Yes |
| Protects the cable after it | Yes, by the fuse | No, needs protection upstream |
| Typical use | Second supply off meter tails, sub-mains | Local isolation of a protected circuit |
| Maintenance | Fuse may need replacing after a fault | Nothing to replace |
| Cost | Higher | Lower |
Things to check before you buy
- Current rating. The isolator must be rated at least as high as the circuit it's on. On a switch fuse, the fuse rating has to suit the cable it's protecting.
- Number of poles. Double pole for most single phase work, triple pole for fans with timers, 3 or 4 pole for three phase.
- Lockable off. Lets you padlock it off during work so nobody switches it back on.
- Enclosure and IP rating. Indoors, a plastic or metal enclosure is fine. Outdoors, pick a weatherproof one.
The design should always follow BS 7671. If you're not sure which device a job needs, ask the counter at our Bridgend branch.
Browse switch fuses, isolator switches and rotary isolators, all with live stock.
Frequently asked questions
Is a switch fuse the same as a fused isolator?
Yes, in everyday use they mean the same thing: a switch and a fuse in one enclosure, giving isolation and overcurrent protection.
Do I need a fused isolator for an EV charger?
Not always. If the charger has its own protective device in the consumer unit, a non-fused isolator is enough for local isolation. If you're taking a new supply straight off the meter tails, you'll normally need a switch fuse to protect the new cable.
Why does a fan isolator need three poles?
A fan with a run-on timer has a permanent live and a switched live as well as the neutral. A triple pole isolator breaks all three, so the fan is fully dead when you work on it.
Need a hand picking one?
Give the Bridgend counter the load, the cable and where it is going, and they will point you at the right device.